1
|
Pollution Grade
|
|
IV
|
|
2
|
Ambient Temperature
|
Maximum Daily Temperature
|
℃
|
40
|
Minimum Daily Temperature
|
-45
|
|||
Maximum Daily Temperature Difference
|
K
|
25
|
||
Average Temperature of the Hottest Month
|
℃
|
30
|
||
Maximum Annual Average Temperature
|
20
|
|||
3
|
Humidity
|
Average Daily Relative Humidity
|
%
|
≤95
|
Average Monthly Relative Humidity
|
≤90
|
|||
4
|
Altitude
|
m
|
1000
|
|
5
|
Solar Radiation Intensity
|
W/cm2
|
0.1
|
|
6
|
Maximum Icing Thickness
|
mm
|
10
|
|
7
|
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
|
m/s
|
35
|
|
8
|
Earthquake Resistance
|
Horizontal Ground Acceleration
|
m/s2
|
2
|
Safety Coefficient of 3 Since Resonance Cycles
|
|
≥1.67
|
||
9
|
Installation Site
|
|
Outdoor
|
|
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).
|
Rated Capacity (kVA)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (W)
|
On-Load Loss (W)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
Acoustic Power Level dB(A)
|
||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
|||||||
30
|
6
6.3 10 10.5 11 |
±2×2.5
±5 |
0.4
|
Dyn11
|
33
|
630/600
|
1.50
|
4.0
|
52
|
50
|
43
|
910/870
|
1.20
|
53
|
|||||
63
|
50
|
1 090/1 040
|
1.10
|
||||||
80
|
60
|
1 310/1 250
|
1.00
|
55
|
|||||
100
|
75
|
1 580/1 500
|
0.90
|
||||||
125
|
85
|
1 890/1 800
|
0.80
|
59
|
|||||
160
|
100
|
2 310/2 200
|
0.60
|
||||||
200
|
120
|
2 730/2 600
|
0.60
|
61
|
|||||
250
|
140
|
3 200/3 050
|
0.60
|
||||||
315
|
170
|
3 830/3 650
|
0.50
|
64
|
|||||
400
|
200
|
4 520/4 300
|
0.50
|
||||||
500
|
240
|
5 410/5 150
|
0.50
|
66
|
|||||
630
|
320
|
6 200
|
0.30
|
4.5
|
|||||
800
|
380
|
7 500
|
0.30
|
68
|
|||||
1 000
|
450
|
10 300
|
0.30
|
||||||
1 250
|
530
|
12 000
|
0.20
|
72
|
|||||
1 600
|
630
|
14 500
|
0.20
|
||||||
2 000
|
750
|
18 300
|
0.20
|
5
|
73
|
||||
2 500
|
900
|
21 200
|
0.20
|
||||||
Note 1: Transformers of “Yyn0” can also be supplied upon demands if the iron core is in the structure of three phases and three columns.
Note 2: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is suitable for Dyn11, on the right for Yyn0. Note 3: Transformers with other loss values can also be supplied upon demands. Note 4: Three-phase transformers with other high voltage tapping range can also be supplied upon demands. |
Rated Capacity (kVA)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (W)
|
On-Load Loss (W)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
Acoustic Power Level dB(A)
|
||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
|||||||
30
|
6
6.3 10 10.5 11 |
±2×2.5
±5 |
0.4
|
Dyn11
|
33
|
565/540
|
1.50
|
4.0
|
52
|
50
|
43
|
820/785
|
1.20
|
53
|
|||||
63
|
50
|
980/935
|
1.10
|
||||||
80
|
60
|
1 180/1 120
|
1.00
|
55
|
|||||
100
|
75
|
1 420/1 350
|
0.90
|
||||||
125
|
85
|
1 700/1 620
|
0.80
|
59
|
|||||
160
|
100
|
2 080/1 980
|
0.60
|
||||||
200
|
120
|
2 450/2 340
|
0.60
|
61
|
|||||
250
|
140
|
2 880/2 740
|
0.60
|
||||||
315
|
170
|
3 440/3 280
|
0.50
|
64
|
|||||
400
|
200
|
4 070/3 870
|
0.50
|
||||||
500
|
240
|
4 870/4 630
|
0.50
|
66
|
|||||
630
|
320
|
5 580
|
0.30
|
4.5
|
|||||
800
|
380
|
6 750
|
0.30
|
68
|
|||||
1 000
|
450
|
9 270
|
0.30
|
||||||
1 250
|
530
|
10 800
|
0.20
|
72
|
|||||
1 600
|
630
|
13 000
|
0.20
|
||||||
2 000
|
750
|
16 400
|
0.20
|
5
|
73
|
||||
2 500
|
900
|
19 000
|
0.20
|
||||||
Note 1: Transformers of “Yyn0” can also be supplied upon demands if the iron core is in the structure of three phases and three columns.
Note 2: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is suitable for Dyn11, on the right for Yyn0. Note 3: Transformers with other loss values can also be supplied upon demands. Note 4: Three-phase transformers with other high voltage tapping range can also be supplied upon demands. |