Products and Services
No.
|
Conditions
|
Units
|
Parameter Values
|
|
1
|
Pollution Grade
|
|
IV
|
|
2
|
Ambient Temperature
|
Maximum Daily Temperature
|
℃
|
40
|
Minimum Daily Temperature
|
-45
|
|||
Maximum Daily Temperature Difference
|
K
|
25
|
||
Average Temperature of the Hottest Month
|
℃
|
30
|
||
Maximum Annual Average Temperature
|
20
|
|||
3
|
Humidity
|
Average Daily Relative Humidity
|
%
|
≤95
|
Average Monthly Relative Humidity
|
≤90
|
|||
4
|
Altitude
|
m
|
1000
|
|
5
|
Solar Radiation Intensity
|
W/cm2
|
0.1
|
|
6
|
Maximum Icing Thickness
|
mm
|
10
|
|
7
|
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
|
m/s
|
35
|
|
8
|
Earthquake Resistance
|
Horizontal Ground Acceleration
|
m/s2
|
2
|
Safety Coefficient of 3 Since Resonance Cycles
|
|
≥1.67
|
||
9
|
Installation Site
|
|
Outdoor
|
|
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).
|
Rated Capacity (KV.A)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (kW)
|
On-Load Loss (kW)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
Acoustic Power Level dB(A)
|
||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
|||||||
30
|
6
6.3 10 10.5 11 |
±5
|
0.4
|
Dyn11
Yzn11 Yyn0 |
80
|
630/660
|
0.30
|
4.0
|
48
|
50
|
100
|
910/870
|
0.24
|
||||||
63
|
110
|
1 090/1 040
|
0.23
|
||||||
80
|
130
|
1 310/1 250
|
0.22
|
49
|
|||||
100
|
150
|
1 580/1 500
|
0.21
|
||||||
125
|
170
|
1 890/1 800
|
0.20
|
50
|
|||||
160
|
200
|
2 310/2 200
|
0.19
|
||||||
200
|
240
|
2 730/2 600
|
0.18
|
52
|
|||||
250
|
290
|
3 200/3 050
|
0.17
|
||||||
315
|
340
|
3 830/3 650
|
0.16
|
54
|
|||||
400
|
410
|
4 520/4 300
|
0.16
|
||||||
500
|
480
|
5 410/5 150
|
0.16
|
56
|
|||||
630
|
Dyn11
Yyn0 |
570
|
6 200
|
0.15
|
4.5
|
||||
800
|
700
|
7 500
|
0.15
|
58
|
|||||
1 000
|
830
|
10 300
|
0.14
|
||||||
1 250
|
970
|
12 000
|
0.13
|
60
|
|||||
1 600
|
1 170
|
14 500
|
0.12
|
||||||
Note 1: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is suitable for Dyn11 or Yzn11, on the right for Yyn0.
Note 2: Transformers with ±2×2.5% of high voltage tapping range can also be supplied upon demands. Note 3: Transformers with 0.69kV of low voltage can also be supplied upon demands. Note 4: Other loss values can also be used upon demands. |