Products and Services
No.
|
Conditions
|
Units
|
Project Requirement
|
|
1
|
Rated Voltage
|
kV
|
10
|
|
2
|
Highest Operating Voltage
|
kV
|
12
|
|
3
|
System Neutral Point Earthing Mode
|
|
Unearthed
|
|
4
|
Rated Frequency
|
Hz
|
50
|
|
5
|
Pollution Grade
|
|
d(Ⅲ)
|
|
6
|
System Short Circuit Current Level (High Voltage Side)
|
kA
|
20
|
|
7
|
Ambient Temperature
|
Maximum Daily Temperature
|
℃
|
40
|
Minimum Daily Temperature
|
-25
|
|||
Maximum Daily Temperature Difference
|
K
|
25
|
||
Average Temperature of the Hottest Month
|
℃
|
30
|
||
Maximum Annual Average Temperature
|
20
|
|||
8
|
Humidity
|
Average Daily Relative Humidity
|
%
|
≤95
|
Average Monthly Relative Humidity
|
≤90
|
|||
9
|
Altitude
|
m
|
≤1000
|
|
10
|
Solar Radiation Intensity
|
W/cm2
|
0.1
|
|
11
|
Maximum Icing Thickness
|
mm
|
20
|
|
12
|
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
|
m/s
|
35
|
|
13
|
Earthquake Resistance
|
Horizontal Ground Acceleration
|
m/s2
|
2
|
Safety Coefficient of 3 Since Resonance Cycles
|
|
≥1.67
|
||
14
|
Installation Site
|
|
Indoor
|
|
Note 1: Values about temperatures in the table must be adjusted accordingly if the lowest ambient temperature is above -25℃.
Note 2: Pollution grade diagram must be provided if the pollution grade is grade IV. |
Rated Capacity (kVA)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (kW)
|
On-Load Loss under Different Insulation System Temperatures (kW)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
||||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
130℃(B)
(100℃) |
155℃(F)
(120℃) |
180℃(H)
(145℃) |
|||||
30
|
6
6.3 6.6 10 10.5 11 |
±2.5
±5 |
0.4
|
Dyn11
Yyn0 |
0.190
|
0.670
|
0.710
|
0.760
|
2.0
|
4.0
|
50
|
0.270
|
0.940
|
1.00
|
1.07
|
2.0
|
|||||
80
|
0.370
|
1.29
|
1.38
|
1.48
|
1.5
|
|||||
100
|
0.400
|
1.48
|
1.57
|
1.69
|
1.5
|
|||||
125
|
0.470
|
1.74
|
1.85
|
1.98
|
1.3
|
|||||
160
|
0.540
|
2.00
|
2.13
|
2.28
|
1.3
|
|||||
200
|
±2×2.5
±5 |
0.620
|
2.37
|
2.53
|
2.71
|
1.1
|
||||
250
|
0.720
|
2.59
|
2.76
|
2.96
|
1.1
|
|||||
315
|
0.880
|
3.27
|
3.47
|
3.73
|
1.0
|
|||||
400
|
0.980
|
3.75
|
3.99
|
4.28
|
1.0
|
|||||
500
|
1.16
|
4.59
|
4.88
|
5.23
|
1.0
|
|||||
630
|
1.34
|
5.53
|
5.88
|
5.29
|
0.85
|
|||||
630
|
1.50
|
6.61
|
5.96
|
6.40
|
0.85
|
6.0
|
||||
800
|
1.52
|
6.55
|
6.96
|
7.46
|
0.85
|
|||||
1 000
|
1.77
|
7.65
|
8.13
|
8.76
|
0.85
|
|||||
1 250
|
2.09
|
9.10
|
9.69
|
10.3
|
0.85
|
|||||
1 600
|
2.45
|
11.0
|
11.7
|
12.5
|
0.85
|
|||||
2 000
|
3.05
|
13.6
|
14.4
|
15.5
|
0.70
|
|||||
2 500
|
3.60
|
16.1
|
17.1
|
18.4
|
0.70
|
|||||
1 600
|
2.45
|
12.2
|
12.9
|
13.9
|
0.70
|
8.0
|
||||
2 000
|
3.05
|
15.0
|
15.9
|
17.1
|
0.70
|
|||||
2 500
|
3.60
|
17.7
|
18.8
|
20.2
|
0.70
|
|||||
Note: Values of on-load loss in this Table is determined by different insulation system temperatures in brackets (please refer to GB1094.11) . Values of on-load loss under other insulation system temperatures (not specified in this Table) must be converted accordingly based on the value of “155℃(F)”.
|
Rated Capacity (kVA)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (kW)
|
On-Load Loss under Different Insulation System Temperatures (kW)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
||||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
130℃(B)
(100℃) |
155℃(F)
(120℃) |
180℃(H)
(145℃) |
|||||
630
|
6
6.3 6.6 10 10.5 11 |
±2×2.5
±5 |
3
3.15 6 6.3 |
Dyn11
Yd11 Yyn0 |
1.44
|
6.00
|
6.36
|
6.80
|
1.0
|
6.0
|
800
|
1.62
|
7.17
|
7.60
|
8.13
|
1.0
|
|||||
1 000
|
1.94
|
8.28
|
8.78
|
9.39
|
0.85
|
|||||
1 250
|
2.34
|
9.86
|
10.4
|
11.1
|
0.85
|
|||||
1 600
|
2.79
|
12.0
|
12.7
|
136.6
|
0.85
|
|||||
2 000
|
3.60
|
14.3
|
15.2
|
16.2
|
0.70
|
|||||
2 500
|
4.23
|
16.8
|
17.8
|
19.1
|
0.70
|
|||||
3 150
|
5.04
|
19.7
|
20.9
|
22.3
|
0.60
|
7.0
|
||||
4 000
|
10
10.5 11 |
6.07
|
23.7
|
26.1
|
26.0
|
0.60
|
||||
5 000
|
7.20
|
28.0
|
29.7
|
31.8
|
0.50
|
|||||
6 300
|
8.50
|
33.3
|
35.2
|
37.8
|
0.50
|
|||||
Note: Values of on-load loss in this Table is determined by different insulation system temperatures in brackets (please refer to GB1094.11) . Values of on-load loss under other insulation system temperatures (not specified in this Table) must be converted accordingly based on the value of “155℃(F)”.
|
Rated Capacity (kVA)
|
Voltage Combination & Tapping Range
|
Connection Symbol
|
No-Load Loss (kW)
|
On-Load Loss under Different Insulation System Temperatures (kW)
|
No-Load Current (%)
|
Short-Circuit Impedance (%)
|
||||
High Voltage (kV)
|
High Voltage Tapping Range (%)
|
Low Voltage (kV)
|
130℃(B)
(100℃) |
155℃(F)
(120℃) |
180℃(H)
(145℃) |
|||||
315
|
6
6.3 6.6 10 10.5 11 |
±4×2.5
|
0.4
|
Dyn11
Yyn0 |
0.990
|
3.40
|
3.61
|
3.86
|
1.1
|
4.0
|
400
|
1.12
|
4.02
|
4.27
|
4.57
|
1.1
|
|||||
500
|
1.28
|
4.92
|
5.22
|
5.58
|
1.1
|
|||||
630
|
1.49
|
5.82
|
6.17
|
6.60
|
1.0
|
|||||
630
|
1.44
|
6.00
|
6.36
|
6.80
|
1.0
|
6.0
|
||||
800
|
1.71
|
7.07
|
7.50
|
8.02
|
1.0
|
|||||
1 000
|
1.98
|
8.28
|
8.78
|
9.39
|
0.85
|
|||||
1 250
|
2.34
|
9.86
|
10.4
|
11.1
|
0.85
|
|||||
1 600
|
2.72
|
11.7
|
12.4
|
13.3
|
0.85
|
|||||
2 000
|
3.42
|
14.3
|
15.2
|
16.2
|
0.70
|
|||||
2 500
|
3.96
|
17.1
|
18.1
|
19.4
|
0.70
|
|||||
Note: Values of on-load loss in this Table is determined by different insulation system temperatures in brackets (please refer to GB1094.11) . Values of on-load loss under other insulation system temperatures (not specified in this Table) must be converted accordingly based on the value of “155℃(F)”.
|