Products and Services
Working conditions:
1. Altitude: ≤1000 m.
2. Ambient temperature:
Highest temperature:+40℃;
Lowest temperature: -40℃;
Maximum average monthly temperature: +30℃;
Maximum average annual temperature: +20℃.
3. Installation environment:
No explosive or corrosive liquid, gas or dust;
No severe vibration or shocking;
Allowing operation partially or completely in water for a specified period.
4. Ground acceleration (ag) caused by earthquake: horizontal <3m/s2, vertical <1.5 m/s2.
5. Waveform of supply voltage: approximate to sine wave.
6. Three phases supply voltage: approximate symmetry
Technical parameters:
★Main technical parameters and performance of buried transformer
1. Model and specification: ZGS11-Z(H)·D -30~630/10, ZGSH15-Z(H)·D-30~630/10
2. Rated voltage: high voltage 6/10kV, low voltage 0.4kV
3. Capacity range: 30~1000kVA
4. Frequency: 50Hz
5. Number of phases: three phases
6. Connection symbol: Dyn11
7. Short circuit impedance voltage: 4%-4.5%
8. Insulation level:
primary side - power frequency withstand voltage: 35kV
primary side - impulse withstand voltage: 75kV
secondary side - power frequency withstand voltage: 5kV
9. Loss: in conformity with S11 series (iron core of silicon steel sheet) national standards; in conformity with S15 series (iron core of amorphous alloy) national standards
10. IP code of shell: IP68
11. Acoustic level: ≤50db
12. Operating environment: basement or pit
13. High voltage connecting pieces: plug-in sealed elbow connector
14. Low voltage connecting pieces: high-quality waterproof and sealing materials
15. Outer shell structure: integrated type, and made up of anti corrosion stainless steel
★Main technical parameters of prefabricated pit
1. Pit is formed by ≥6mm punch-forming steel plates.
2. The whole pit is processed by hot galvanizing.
3. Cover of pit is made up of cement precast slab, with an openable access hole
★Main technical parameters of high voltage switchgear
1. Rated voltage: 12kV
2. Rated frequency: 50Hz
3. Rated current: 630A
4. Rated short time withstand current: 20kA/2s
5. Rated peak withstand current: 50kA
6. Rated short circuit making current: 50kA
7. Rated power frequency withstand voltage (phase to ground/breaking): 42/48kV (1min)
8. Rated impulse withstand voltage (phase to ground/breaking): 75/85kV
9. IP code: IP34
★Main technical parameters of low voltage switchgear
1. Rated voltage: 400V
2. Rated frequency: 50Hz
3. Rated current of major loop: 100A~2000A
4. Rated short time withstand current: 15kA, 30kA
5. Rated peak withstand current: 30kA, 63kA
6. IP code: IP34