Working conditions:
1. Ambient temperature: +40°C~-25°C; 24h average temperature: ≤ 35°C
2. Altitude: ≤1000m
3. Gradient: ≤3°
4. No dust, or no corrosive or inflammable gas, vapor or salt mist
5. Earthquake horizontal acceleration: ≤3g
6. Please consult us if clients have other different conditions
Items | Units | Load Switch | “Load Switch + Fuse Protector” Combined Device |
Rated Voltage | kV | 12 | 12 |
Rated Current | A | 630 | 125 |
Rated Active Load Breaking Current, Rated Closed Loop Breaking Current |
A | 630 | |
Rated Short Time Withstand Current (4S) | kA | 20 | |
Rated Short Circuit Making Current | kA | 50 | |
Rated Peak Withstand Current | kA | 50 | |
Rated Cable Charging Breaking Current | A | 10 | |
Rated Breaking No-Load Transformer | kVA | 1600 | 1600 |
Rated Breaking Take-Over Current | A | 2000 | |
Rated Short Circuit Breaking Current of Fuse Protector | kA | 31.5 (Expected Value) | |
1min Power Frequency Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) | kV | 42/48 | 42/48 |
Lightning Impulse Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) | kV | 75/85 | 75/85 |
Mechanical Life | Number of Times | 5000 | 5000 |
Electric Operation Voltage | V | AC/DC 220V | |
Rated Voltage of Shunt Release | V | AC/DC 220V |
Items | Units | Load Switch | “Load Switch + Fuse Protector” Combined Device |
Rated Voltage | kV | 12 | 12 |
Rated Current | A | 630 | 125 |
Rated Active Load Breaking Current, Rated Closed Loop Breaking Current |
A | 630 | |
Rated Short Time Withstand Current (4S) | kA | 20 | |
Rated Short Circuit Making Current | kA | 50 | |
Rated Peak Withstand Current | kA | 50 | |
Rated Cable Charging Breaking Current | A | 10 | |
Rated Breaking No-Load Transformer | kVA | 1250 | 1250 |
Rated Breaking Take-Over Current | A | 1700 | |
Rated Short Circuit Breaking Current of Fuse Protector | kA | 31.5 (Expected Value) | |
1min Power Frequency Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) | kV | 42/48 | 42/48 |
Lightning Impulse Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) | kV | 75/85 | 75/85 |
Mechanical Life | Number of Times | 2000 | 2000 |
Items | Units | Values | |
Rated Voltage | kV | 12 | |
Rated Current | A | 630 | |
Rated Frequency | Hz | 50 | |
Rated Short Time Withstand Current | kA | 20 | |
Rated Short Circuit Duration Time | S | 4 | |
Rated Peak Withstand Current | kA | 50 | |
Rated Short Circuit Duration Time of Earthing Switch | S | 4 | |
Rated Peak Withstand Current of Earthing Switch | kA | 50 | |
Rated Insulation Level | 1min Power Frequency Withstand Voltage (Valid Value) | kV | (Phase to Phase, Phase to Ground) 42; (Breaking) 48 |
Lightning Impulse Withstand Voltage (Peak Value) | kV | (Phase to Phase, Phase to Ground) 75; (Breaking) 85 | |
Rated Pressure of SF6 Gas (meter value at 20°C) | Mpa | 0.04 | |
Leak Rate of SF6 Gas | 1% | ||
IP Code | IP3X |