Technical Features:
1. DSP+CPLD digital control; response time <10ms
2. Advanced major circuit topology and control algorithm, with higher precision and stability
3. Modular design, convenient for manufacturing debugging
4. Multifunctional touch screen, to intelligently monitor operation status and parameters of power grid
5. Convenient parallel hybrid, to increase capacity
6. Perfect bridge arm overcurrent and protection function
7. Convenient to use, and easy to operate and maintain
Mode of Connection
|
3-phase 3-wire or 3-phase 4-wire
|
|||
Input Voltage
|
3×380V±10%
|
|||
Input Frequency
|
50Hz±2%
|
|||
Dynamic Compensation Response Time
|
Complete Response Time<10ms
|
|||
Switching Frequency
|
16kHz
|
|||
Function Set
|
Only Compensating Harmonic Wave, Only Compensating Reactive Power, Compensating both Harmonic Wave and Reactive Power; Free Switch of Manual and Automatic Operation
|
|||
Harmonic Compensation Times
|
2-25 Times
|
|||
Protection Mode
|
DC Overvoltage IGBT Overcurrent Device Temperature Protection
|
|||
Overload Protection
|
Automatic current limiting at setting value, no overload
|
|||
Cooling Mode
|
Intelligent Air Cooling
|
|||
Noise Level
|
<65db (in the Cabinet and operated at rated conditions)
|
|||
Ambient Temperature
|
-10℃ ~ +45℃
|
|||
Ambient Humidity
|
<85%RH, no condensation
|
|||
Installation Site
|
Indoor
|
|||
Altitude
|
≤1000m (reducing capacity upon higher altitude)
|
|||
Wiring Method
|
Incoming and Outgoing Lines both at Upper Part
|
|||
IP Code
|
IP20
|
|||
Intelligent Communication Interface
|
Add-on Module
|
|||
Remote Monitoring
|
Optional
|
|||
Dimension (mm)
(W X D X H) |
30A
|
60A
|
75A
|
100A
|
600 X 500 X 1500
|
600 X 500 X 1500
|
600 X 500 X 1800
|
800 X 600 X 2200
|
|
Weight (kg)
|
3-Phase 4-Wire
|
3-Phase 3-Wire
|
||
30A, 50A
|
75A, 100A
|
30A, 50A
|
75A, 100A
|
|
280
|
360
|
240
|
290
|
|
Remark:
1. Compensating current can be determined through actual test data, or measured through power system details (single line drawing, transformer, load condition, etc.) 2. 3-wire system should be configured with 2 or 3 CT (used for phase A and phase C), and 4-wire system should be configured with 3 CT (used for phase A, phase B and phase C) |